Technical reference

      
Electrical code notescode ref
 Enumercated  
    Building code = electrical 18-27article
*  Demand factor= The ratio of the maximum demand of a system,or part of a system,to total connected load of a system or the part of the system under consideration
100
*  Seperately derived system= a permise wiring system whose power is derived from battery,a solar voltaic system,or from generator  transfomer or convertor winding
100
*  Feeders = 125% of the continuous load215.2
*  Lighting load demand factor220.11
*  Purpose of code to practical safeguarding of persons and property from hazards arising from use of electric90.1
code is minimum requirements13-2-010
 *ComEd meter height 30":60" 
 *Show windows 1 recp per 12' linear ft.   [ Show window track 200va per' 1.7a]210.62
 *Sign 200va per' 1.6amp per '220.3 (6)
 *Dwelling  = receptacles & general 180va pre sq ' 1.5 a220.3 (a)
   1ckt per 500 sq '220.3 (11) (1)
    VA general load calculation dwelling 3va per sq 220.3 (a)
    Dwelling shall have receptacle front & back560.6 (e)
    Each commercial building shall be provided w/ at least one outlet in an accessible location at each entrance to each tenant space for sign on separate dedicated ckt600.5 (a)
 *All habitable rooms210.70. (1)
 *Receptacle spacing560.6
   12'Receptacle every 12' 210.50.1
    Area with glass wall may substitute floor receptacles within 18" of wall210.52 (3)
   2'Wall of of 2' must have recp.                                      210.52 (2) a210.5.2
    Stairway,hallway 10' or more (1) receptacle            560.6 (h)210.52 (b)
    Receptacle within 25' of AC  GFIC210.63
    Where light outlets are install interior stairway and the difference between floor level is 6 steps,there shall be a switch at each floor210.70 (b)
    Countertop space separated by range,refrigerator,or sink,shall be considered as separate counter space on applying the requirements of (1) (2) (3)560.6 (4)
    In every deweliing containing two or more units,the owners having control of the stairs,vestibules,corridors and common area shalll provide and maintain illumination560.7 (2)
 *Kitchen2Separate appliance circuits       (exhaust can't be connected)210.11 (c)  (1)
   24"Counter top 12"between recp.     >12" : 12"< must be GFIC210.52 (c ) (1)
   24"Peninsular , island210.52  (c )  (3)
   2Appliance ckts kitchen                    [exhaust cannot be tap from appliance ckt 210.52]210.11
 *Bath1GFIC recp. No more then 2 bathroom on 1 ckt  210.8 (b) &210.11(1)
 *Laundry1GFIC      560.5 ( c )      1,500va 12.5a210.11  (f)
    Household cooking     560.16 (b)560.10 (2)
 *BedroomBedroom shall be protected by arc-fault current interrupter210.12
    An arc-fault circuit interrupter is a device intended to provide protection from the effects arc faults by recognizing characteristics unique to arcing and by functioning to de-energize the circuit when an arc fault is detected.210.12
 *Ground-fault protection570.8
    All 125 v,single phase,15 & 20  amp receptacle ,installed in bathrooms,garages,counter top spaces,unfinished basements and locations shall have gfic protection570.8
 *Working space 210.26
   30"width110.26
   36"cable manhole working space370.52
   36"depth ,front 4' with exposed live parts on the other side         [ 601 :2,500v]110.26
   48"depth ,                                                                                                          [ 2,501  :  9,000v]110.34 (a)
   60"depth ,front 4' with exposed live parts on the other side        [ 9,001 : 25,000v]110.34 (a)
   6'depth                                                                                                           [25,001 :  75kv]110.34 (a)
   8'depth                                                                                                          [75kv : ^]110.34 (a)
   78"height              110.26 (e)
   3'Where area is acess is required on back of encclosed equipment 3' horizontally110.26 (1)
 *Clearance overhead drop 225.18
   10'sidewalk 225.18
   12'residential property & driveway less then 300v 225.18
   15'over 300v 225.18
   8'above roof 225.19
   3'from window,door,porch,balconies,ladder,stairs 225.30 (d)
   10'service entrance point225.18
   10'no overhead over pool & extending 10' horizontally from inside wall of pool,    bond grid680.8 & 680.21
   18'over public street 225.18
 *Minimum burial cover requirements  300.5
   30"600v:22kv direct burial300.5
   18"600v:22kv nonmetallic conduit300.5
   18"Direct burial cable shall be protected with raceway 18" below grade300.5 (d)
   6"rigid hw300.5
    underground service entrance conductors can share same trench w/ gas,cable,phone. Electric shall have a 12" seperation from othersComEd
    Primary & secondary pipe and duct = one spare conduit for each secondary runComEd
   3"Length of free conductor opening less then 8"300.14
   6"Length of free conductor opening 8" or ^300.14
 *General requirements 
    NEC=permits use of conventional box & fittings in pledumn ceiling.No arch causing devices in ceiling.Switch used in ceiling shall be vapor tight 
    Chicago:pledumn = compression fitting,no holes in boxes,gasket blanks300.22
    Emergency lighting shall be provided in commercial space 1,000sq' ^700.9
    5,000 sq' ^ shall have automatic lighting control Illinois Energy Code 
    Lighting watt per'=1.3 
    Main bonding jumper=From ground buss to line side of neutral disconnect250.24
    Al nipples to be bonded both sides250.91
    Auxiliary gutters shall be permitted to supplement wiring space at meter centers,distribution centers374.1
    Induced current in metal raceway: All phase conductor and ground conductors and all equipment grounding conductors shall be grouped together300.20 ( a)
    wire charts use 75°coloumn current310
    conductor shall not be bend to a radius less then    8 * dia. Non-shielded,    12* shielded 300.34
    Nonincendive circuit = no arc504.2
    Intrinsically safe=a circuit in which any spark or thermal effect is incapable of causing ignition >1.2v,.1a,20micro joules    500.4 (e)504.2
    RTD=resistance tempature device 
    Circuit breakers used as switches shall be listed "SWD"  240.83 (d)
    Load calculations    demand 220.11220.3 (a)
    Voltage drop E=I*R    Voltage=current*resistance page 586               Tables 900 table 8
    Conductor bending radius 8* diameter nonshielded 12* shielded300.34
    Repair garage up to 18" above floor is considered class 1 511.3 (a)
    Office furniture=3/8 flex605.7 (b)
    Dewlling 5 units or more must have EM lights 230
    In office count neutral in load cal.   [ Because of non-linearl load]220.22
    Parallel  runs must be same length and materials310.4
    In sight 50' or less100